📄 Extracted Text (1,181 words)
CREST
me ruAigirst SYST,MC IN ,
?"\,
Jim Eichorst
JB Henderson Construction
Albuquerque, NM 87123
August 8, 2012
re: Zorro Ranch — PoolPak AW1800
Dear Mr. Eichorst,
Executive Summary — previous report dated July 30th provides additional, technical details
The Poolpak unit finally gained operational status Thursday night, August 2nd and apparently has maintained it
to date. Poolpak's service manager provided key bits of information on Wednesdahy that helped to finalize the
repair on Thursday. Details follow.
Reheat Mode (heating/dehumidifying)
The check valve at the pool water condenser (PHX or WCC) sticks — intermittently, partially or completely is
unclear as operation of the unit has been erratic for sometime according to reports from property manager Bryce
Gordan and JBH tech Richard.
The bypass valve piped in parallel with the PHX actuated valve receives power, yet it does not open. A
magnetic donut drew the valve open allowing full flow of refrigerant through the entire circuit. Head pressures
immediately dropped to normal, expected levels.
AC Mode (cooling)
Previous to replacing the refrigerant charge this mode exhibit high discharge (head) pressures similar, yet not
the same as with the reheat mode. With new refrigerant the head pressures are nearly the same as in reheat
mode which is expected as the return air temperature and the water temperatures are similar.
Refrigerant Replacement
Previous work on the unit may have resulted in inadvertent introduction of non-condensables into the
refrigerant circuit. Poolpak disclosed that they cannot say what valves open in DWH mode and that the manual
mode for opening valves may not allow full access to all sections of the refrigerant circuit. They instructed the
use of magnetic donuts at least two solenoid valves. Instead, the installation of a service valve at the bottom of
the reheat coil and fully opening the stems on the liquid line solenoid valve and the PHX solenoid valve
provided a complete evacuation of the refrigeration system.
Hot Water Coil
Flex connections swapped to introduce hottest water to entering air. Valve rewired to allow direct operation
through the Poolpak unit.
TELEPHONE 1
QUALITY ENGINEERED MECHANICAL EQUIPMENT
SERVICED FROM CONCEPTUAL DESIGN THROUGH OWNER OPERATION
EFTA00315611
Wall Sensor (Poolpaki
Damaged by Crest while rewiring ECI alarm circuit. Wall sensor is placed on an interior wall in the pool room
making it non-functional. It is designed for placement on a door or window sill. Rather than moving and
rewiring it, insert a 10K resistor at teminals 10 & 11 on the field wiring terminal in the Poolpak electrical panel.
The resistor will provide a steady read out of 82F at the interface panel and clear the unit alarm on Mr. Gordan's
computer.
The unit should maintain +1- IF of air temperature setpoint and +5% of the humidity setpoint, or something
fairly close when monitored over a period of an hour once a steady state of operation is reached. In other
words, should doors be left open resulting in a drop in temperature and corresponding rise in humidity it may
take more than an hour to reach a steady state.
Exhaust
Install a direct drive, inline exhaust fan with sufficient static pressure capacity to push air to whatever exhaust
trunk there may be near the mechanical room. Duct should be size at least 10" if not 12" round or 10 x 10
square or similar. Fan to exhaust a minimum of 400 cfm.
Outside Air
Once exhaust airflow is established, move the OA quadrant damper to a position that provides a slight negative
in the pool space. Fix and mark the handle position.
Electrical
Crest replaced the #00 wire (100 amp rating) with #8 wire (75 amp wire) and the 100 amp fuses with 70 amp
fuses. Factory MCA rating is 60 amp, yet 60 amp fuses are not available in the blade style used in the existing
disconnect. The owner should direct whether replacement of the disconnect is desired. The #8 wire will be
protected with 60 amp fuses in any case if the disconnect is replaced.
Supply Air Grilles
High recommendation that the floor grilles be changed to similar style yet with a 30-45 degree deflection that
pushes the air at the bottom of the glazing on the doors. This change will wash the windows and protect future
windows from failing as the present windows have.
Secondary concern is that no air seems to be introduced at the ceiling grilles. It is unclear as to how the duct is
run, whether balancing dampers are installed and accessible and whether the lack of airflow can be fixed.
Address this issue if condensation on the ceiling occurs in winter. If so, add a grille to the center ceiling panel
as well if air can be directed to this section of ductwork.
Unit Size
Unit sizing should be reviewed via observation over time (i.e. months) and with use of the space history. The
present unit when operating properly should be able to meet the space load most of the time. Additional
measures may be needed to supplement the unit performance. Pool dehumidification heat pump units operate
within a dynamic system of fans, pumps, coils and controls. All components of the system must operate
correctly for the dehumidification heat pump to operate correctly. Note that other manufacturers such as
TELEPHONE 2
QUALITY ENGINEERED 1442EVILINWAL EQUIPMENT
SERVICED FROM CONCEPTUAL DESIGN THROUGH OWNER OPERATION
EFTA00315612
CR ES-7
T\
MI CHANICAL SYSTEMS t.
?-\
7005 FOURTH ST IVW, LOS RANCHOS, NM 87107
Dectron, which is represented by Crest, offer single phase units that are substantially larger and will meet the
space capacity for this site.
Waterflow — Pool
No pool water piping is connected at factory provided ports. The connection of pool water is highly
recommended. Should water be piped to the unit in its present state, then Poolpak recommends removing the
PHX and its associated valve from the refrigerant loop and replacing the Bypass valve and piping tee with a
piece of straight copper. This work is not needed if the magnetic donut hold the Bypass valve open.
Remove the neutral wire of the Bypass valve from its wire nut connection with the PHX valve.
Waterflow — AC Heatpump Loop
Install a 1" flow meter to verify loop flow.
Refrigeration Systme Readings
Cooling Mode Heating Mode
Compressor Discharge (6" away) I 84F 192F
Compressor Suction (6" away) 48F 5IF
Amp Draw 25.5 amps 25.5 amps
Head 280 psi (90F) 290 psi (95F)
Suction 60 psi (30F) 64 psi (39F)
Water Loop 76Fin/94Fout NA
TXV 44F 46F
Return Air 84F 86F
Humidity 49% 53%
Supply Air (should have been recorded)
Sight Glass Small trail of bubbles present often, yet factory advises to ignore bubbles
if super heat is close to factory desired 16F. Factory charge of 20# 13oz
of R-22 was installed. Unit is fully charged. Short of any other indicator
of a problem, ignore slight bubbles in the sight glass. Inspect for
onstant bubbles in the sight glass that persist for more than a minute.
They may indicate a refrigerant leak.
Respectfully,
Jim Asperger
TELEPHONE 3
QUALITY ENGINEERED AOICILINIOAL EQUIPMENT
SERVICED FROM CONCEPTUAL DESIGN THROUGH OWNER OPERATION
EFTA00315613
ℹ️ Document Details
SHA-256
1030cf67d8ecb7b77880e1161156613282d1ba091922eefd3fa31924bbe7cc60
Bates Number
EFTA00315611
Dataset
DataSet-9
Document Type
document
Pages
3
Comments 0