Diesel Generators 10. 3200 Kw I Alternators 6.3500 Kra I Transfer Switches I Fuel Tanks I Trailers I Engles Parts I Alternator Parts
SONO I KOHLER I EROIRYROINN I HIPCMER I JCI-ei CEERE I CUMMINS I PERO'S I MliSODSHI I VOLVO I STA/AFCRO I LEROY SOMER
GENERAL
POWER
GP J8OUC3 Engine JOHN DEERE, 4045HFS82, EPA/CARB Tier 3
Alternator LEROY SOMER , LSA43.2L8
80 KW JOHN DEERE GENERATOR
80 KW ! 100 KVA DIESEL GENERATOR SET. FULLY PACKAGED:
• JOHN DEERE Heavy duty diesel engine. 4 stroke. 1800rpm. Turbo. EPA
• LEROY SOMER brushless alternator. IP23 protection. Insulation class H
• SCHNEIDER. Main line circuit breaker. wired. maximum output rated
• EPA Tier 3 compliant engine per U.S. Environmental Protection Agency
• Digital auto-start control panel. CE and UL compliant
• Incorporated metallic fuel tank for day use
• Auto Start control feature included for interoperation with ATSIAMF
• 12V charging alternator and 12V DC electric starter motor
• 12V charged DC starting battery with electrolyte and cables
• Dry type air filter. fuel filter and oil filter elements installed
• Mechanically welded chassis with vibration isolators
• Each unit prototype and individually factory load bank tested
• The generator accepts 100% rated load in one step as per NFPA110
and meets IS08528.5 class G-3 for transient response
• Compliant with ISO3046. ISO8528. BS4999. BS5514. BS500OPT99.
AS1359. IEC34. UTE5100. VDE0530 and IS09001:2000
AVAILABLE ACCESSORIES AND OPTIONS:
• Steel or Aluminum weather proof. sound attenuated enclosures
• UL142 listed. double wall fuel tanks from 50 to 10.000 Gal
• UL1008 listed, automatic transfer switches from 50 to 3000 Amp
MI compliant heavy duty road trailers from 3000 to 30000 Lbs
• Automatic battery chargers. Engine pteheaters. Remote annunciators
and many more
Power ESP Power PRP
Voltage kWelcVA kWe,kVA Standby Amps Dimensions - Open Weight - Open
480/277 801100 73 / 91 120
460/265 801100 73/91 126 Length: 1950mm [77in) 1170kg [2579lbs] Net
440/254 78/ 98 71189 129 Width: 1084mm [43in] 1370kg [3020lbs] Gross
240/139 75 / 94 68/85 226 Height: 1350mm [53in)
230/133 70/ 88 64/80 221
220/127 78 / 98 71 /89 257
208/120 74 / 92 67 / 84 255
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications. in accordance with ISO
8528.1.
ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-
1. Overload is not allowed.
TERM OF USE
Standard reference conditions ESP)PRP 25 C°/25 C° Air Inlet Temp. 1000 m/1000 m m A.S.L. 60 % relative humidity.
WEATHER PROOF / SUPER SILENT ENCLOSURES
Model dB(A)@31t dB(A)@231t Dimensions - Enclosed Weight - Enclosed Tank
Length: 2554mm [101in]
1590kg [35051bs]
Width: 1150mm 145in] 190 L
M129 78 68 1790kg [39461bs]
Height: l 680mm (661n] 50 Gal
GENERAL POWER LIMITED, INC
EFTA01097440
Diesel GenerMors 10.3200Kw 1 ANNTIMOlt 6.3600 Kra I Tress* Snitches I Fuel Tanks I 'Ewen I Engine Puts I Alternator Pelts
SONO I KOHLER I eROPDCROWN I HIPONER I JON DEERE I CUMMINS I PERKIN I MITSUSGHI I VOLVO I STAMFORD I LEROY SUMER
GENERAL
POWER
ENGINE SPECIFICATIONS
JOHN DEERE 4045HFS82,
Engine model 4-strokes, TURBOCHARGED, AIEVAIR, 4 Cylinders,
U.S. EPA / CARS TIER 3
Cylinders-arrangement 4-L
Displacement (C.I.) 4.48
Bore (mm) X Stroke (mm) 106 X 127
Compression ratio 19 : 1
DATA Speed (RPM) 1800
Pistons speed (mis) 7.62
GENERAL DATA Maximum stand-by power at rated RPM (kW) 94
Frequency regulation (%) +/-0.5%
BMEP (bar) 12.8
Governor type ELECTRONIC
Exhaust gas temperature (°C) 576
EXHAUST SYSTEM Exhaust gas flow ([is) 307
Max. exhaust back pressure (mm CE) 750
Fuel consumption 110% load 25.06 Uhr [6.6 gal/hr]
Fuel consumption 100% load 22.8 Uhr [6.0 gaUhr]
FUEL SYSTEM Fuel consumption 75% load 20.31 Uhr [5.3 gal/hr]
Fuel consumption 50% load 14.98 Uhr [3.9 gaUhr]
Maximum fuel pump Itchy 59.29 Mr [15.6 galihr]
Oil capacity (L) 13
Min. oil pressure (bar) t.05
OIL Max. oil pressure (bar) 3
Oil consumption 100% load (L/h) 0.06
Carter oil capacity (L) 12
THERMAL BALANCE Heat rejection to exhaust (kW) 89.22
Radiated heat to ambiant (kW) 11.46
Haet rejection to coolant (kW) 52.55+11.8
AIR INTAKE AIR INTAKE_entree_max% 375
Intake air flow (Us) 110.67
Emissions PM (g/kWh) 0.25
EMISSIONS Emission CO (g/kW.h) 1.47
Emissions HCNOx (g/kWh) 3.43
Emission HC (g/kW.h) 0.14
GENERAL POWER LIMITED, INC
EFTA01097441
Diesel Generators 10.3200 Kw I Altemators 6.3600 Kra I TranslerSvilleMs I Fuel Tanks I Trailers I Engine Parts I Allema!weans
SDVO I KOKER I BRINLIYROWN I IIICKYAER OCIISCEERE I CUMMINS I PERKINS I VITSVEL.SHI I vas° I STAMFORD I LEROY SOV.ER
GENERAL
POWER
ALTERNATOR SPECIFICATIONS
Alternator brand LEROY SOMER
Alternator LSA43.2L8
Number of phase 3
Power factor (Cos Phi) 0.8
Altitude (m) <1000
Overspeed (rpm) 2250
Number of pole 4
DATA Excitation system Sell Excited
Insulation class / Temperature class H H
GENERAL DATA Automatic Voltage Regulator R250
Total harmonics TGHITHC <2
Wave form : NEMA=TIF-TGH/THC <50
Wave form : CEI=FHT-TGH/THC <2
Number of bearing 1
Coupling DIRECT
Voltage regulation 0 to 100% +1-0.5%
Recovery time (Delta U = 20% transitoire) (ms) 500
Continuous Nominal Rating 40°C (kVA) 95
Standby Rating 27°C (kVA) 107
Efficiencies 4/4 bad (%) 91.1
Air flow (cfm) 0.32
Short circuit ratio (Kcc) 0.4
Direct axis synchro reactance unsaturated (Xd) (%) 293
Quadra axis synchro reactance unsaturated (Xq) (%) 176
Open circuit time constant (Tdo) (ms) 1431
Direct axis transient reactance saturated (%) 10
Short circuit transient time constant (ms) 50
OTHER Direct axis subtransient reactance saturated (XV) (%) 5
Subtransient time constant (7d) (ms)
DATA Quadra axis subtransient reactance saturated (X-q) (%) 6.3
Zero sequence reactance unsaturated (Xo) (%) 0.8
Negative sequence reactance saturated (X.2) (%) 5.8
Armature time constant (Ta) (ms) B
No load excitation current (io) (ms) 0.4
Full load excitation current (Ic) (A) 1.6
Full load excitation voltage (uc) (A) 29
Recovery time (Delta U = 20% transitoire) (ms) 500
Motor start (Delta U = 20% perm. or 50% trans.) (ms) 269
Transient dip (4/4 charge) - PF : 0.8 AR (%) 14
No load losses (kW) 2.06
Heat rejection (kW) 7.57
___LEROY® GENERAL POWER LIMITED, INC
1350 NW 78 Avenue / Miami, Florida 33126
EFTA01097442
Diesel Generators 10.3200 Kw I Attemstors 6.3500 Kra I TransferSwitches I Fuel Tanks I Trailers I Engine Parts I AllematorPaits
SULIO r KOHLER I BROADCROWN I !LIPNER r KOHL`rl GEER& I CUMI.INS I PERQIS I MIT9JEKSHI I VOLVO I STAMFORD I LEROY SOMER
GENER
POWER
CONTROL PANELS
Standard NEXYS
sin
NIEXYS Specifications : Frequency meter. Ammeter. Voltmeter
Alarms and faults : Oil pressure, water temperature,
Overcrank. Overspeed ( >60 kVA). Min/max alternator, Low
IMO fuel level. Emergency stop
Engine parameters : Hours counter, Engine speed, Battery
• e voltage, Fuel level, Alr preheating
0 'lion TELYS2
Specifications : Frequency meter, Ammeter. Voltmeter
Alarms and faults : Oil pressure. water temperature. No start-
up. Overspeed. Minimax alternator. Minimax battery voltage.
Low fuel level, Emergency stop
Engine parameters : Hours counter, Oil pressure. Water
temperature, Engine speed. Battery voltage. Fuel level
Remote monitoring and control
ACCESSORIES AND OPTIONS
0•ti011 Automatic Transfer Switches, UL1008 listed: 100 to 4000 AMPS
r
ASCA With a Series 300 transfer switch, you get a product backed by
ASCO Power Technologies, the industry leader
EMERSON •True double-throw operation: single solenoid design is inherently
interlocked & prevents contacts from stopping between sources
•Easy-to-read flush-mounted control and display panel provides
LED indicators for switch position and source availability
U •Standard engine exerciser for weekly automatic testing with or
without load
•UL 1008 listed for Transfer Equipment and CSA C22.2 listed
•NFPA 110 for Emergency & Standby Power & the National
Electrical (NEC) Articles 700. 701 and 702
I
0 • ion Fuel Tanks, UL142 listed: 50 to 5000 GAL
•UL listed. Secondary containment tank meeting UL 142 tank
requirements
•NFPA compliant. Designed to comply with the installation
standards of NFPA 30 and NFPA 37
LISTED •Emergency pressure relief vents. Meets UL requirements: ensures
adequate venting of inner and outer tank under extreme pressure
and/or emergency conditions
•Electrical stub-up area with removable end channel
•Normal vent • Inner tank emergency vent sized to UL 142 specs
•Direct reading mechanical fuel gauge • Fuel in basin switch
•Satin black paint finish
GENERAL POWER LIMITED, INC
1350 NW 78 Avenue Miami, Florida 33126
EFTA01097443
Diesel Generators 10.3200 Kw I Alternators 0.3500 Kra I TransferSwitches I Fuel Tanks I Trailers I Engine Parts I MarnelorParts
SOMO I KOHLER I BROADCROWN I HIPOMER I !GIN DEERE I CUMMINS I PERMS I MITSUDSHI I VOLVO I STAMFCRO I LEROY SOMER
Weatherproof / Super silent
M129 Enclosure
STANDARD FEATURES
▪ 12 gauge electro-zinc powder coated steel for maximum corrosion resistance (Phosphatizing degreasing. Non-chromic
passivafion, Osmosis purified rinsing and High durability polyester resin thermosetting powder paint)
■ 29dB(A) Internal-mounted critical silencer and flexible exhaust connector offering maximum component life and
operator safety
■ Fade-. scratch-, and corrosion-resistant. Automotive-grade textured finish resulting in advanced corrosion and
abrasion protection as well as enhanced edge coverage and color retention
■ Up to 51mm (2in) Acoustic insulation with hydrocarbon sealing film that meets FMVSS 302 flammability classification
and repels moisture absorption
■ Interchangeable modular panel construction. Allows complete serviceability or replacement without compromising
enclosure design
■ Service access. Multi-personnel doors for easy access to generator set controller. breaker and service points
■ Externally mounted emergency stop button, Single point lifting hook and Tamper proof "securit" viewing control window
■ Cooling air discharge. Weather protective design featuring a vertical air discharge outlet grille. Redirects cooling air up
and above enclosure to reduce ambient noise
■ Cooling/combustion air intake with a horizontal air inlet. Sized for maximum cooling airflow
■ Heavy duty Polyamide plastic hinges. Dichromate galvanized bolting and Stainless steel rivets for lifetime longevity
■ Meets and exceeds NFX41002 Salt spray test, NFT30049 UV Performance test, NFT30038 Paint adhesion test and
2000/14EC Low sound directives
C •
EI
•
GENErtiaL
EIR
•
I
www.genpowerusa.com
Sound Level
Dimensions Weight Fuel Tank
Model
dB(A)@31I d8(A)(6)23ft LW A (in) (Lbs) (Gal)
GP J8OUC3 78 68 N/A 101 x 45 x 66 3505 50
GENERAL POWER LIMITED, INC
EFTA01097444
ℹ️ Document Details
SHA-256
1a3f23d4b40a43617f3eb41199e59899cae04aff93a36c4b5869a099a0152bf5
Bates Number
EFTA01097440
Dataset
DataSet-9
Type
document
Pages
5