EFTA00798754
EFTA00798769 DataSet-9
EFTA00798874

EFTA00798769.pdf

DataSet-9 105 pages 19,336 words document
P17 V11 V16 P22 P24
Open PDF directly ↗ View extracted text
👁 1 💬 0
📄 Extracted Text (19,336 words)
CAT Project Submittal For LSJE, LLC - ST. THOMAS Two (2) Caterpillar Model D125 - 8 Engine Driven Generator Set Warren Cat ID No.: M0114821, M0114822 Warren Cat EA No.: CE36505, CE36506 CATERPILLAR EFTA00798769 LSJE, LLC - ST. THOMAS 6100 Red Hook Quarter B3 St. Thomas, VI 00802 - 1348 Project Submittal 125 kW Electric Generator Set Little St. James Two (2) Caterpillar Model D125 - 8 Customer Purchase Order No.: CBO Warren Cat ID No.: M0114821, M0114822 Warren Cat EA No.: CE36505, CE36506 Warren CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 19 July 2018 EFTA00798770 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 CONTENT SECTION DESCRIPTION SCOPE OF SUPPLY Standard Consist Selected Caterpillar Options Documentation Start Up & Commissioning Warranty II GENERATOR PACKAGE C7.1 Generator Set — Electric Power III ALTERNATOR DATA Generator Data Operating Chart IV TECHNICAL DATA (Cut Sheets) Weather Protective Enclosure ADEM EMCP 4.2 Controller Permanent Magnet Generator Integrated Voltage Regulator Excitation Module Coolant Heater Circuit Breaker Application Breaker Curves Ground fault Relay Battery Charger Battery UL Listed V MECHANICAL DRAWINGS VI ELECTRICAL DRAWINGS VII START UP AND COMMISSIONING CHECK LIST VIII CATERPILLAR WARRANTY Note: Images shown in this document may not reflect the actual configuration. EFTA00798771 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION I SCOPE OF SUPPLY The following is a listing of the equipment and services to be provided with each of two (2) sets: Item 1 One (1) Caterpillar Model D125 - 8 diesel engine generator sets with the following configuration: Configuration EPA STATIONARY EMERGENCY PRIME POWER APPLICATION Rating 114 ekW, 0.8 pf, 208 / 120 Volt, 3 Phase, 60 Hz, 1,800 rpm Unit Consist Diesel Engine: Model C7.1-ELEC Alternator: Frame LC3114J Single Bearing, Random Wound Standard Consist for C7.1 PGABR ENGINE PACKAGE DESCRIPTION ENGINE Electrical system,12 VDC Coolant and lube drains piped to the edge of base D125-8 includes ADEM A4 electronic engine control with Speed Adjust thru EMCP Tier 3 EPA Approved Emissions Certified INTEGRATED VOLTAGE REGULATOR (Digital): EM10 Excitation Module Voltage within +/- 0.25% at steady state from no load to full load Provides fast recovery from transient load changes CHARGING SYSTEM CAT Premium High Output Battery with rack & cables Installed (wet); 1000 CCA; 90amp hr;12V EFTA00798772 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION I SCOPE OF SUPPLY (continued) Standard Consist for C7.1 PGABR (continued) CONTROL SYSTEM CONTROL PANEL NEMA 1 enclosure with hinged door Wiring loom DC and AC wiring harness EMCP 4.2 controls including: Run / Auto / Stop Control Speed Adjust Engine Cycle Crank Emergency Stop pushbutton EMCP 4.2 controller features: 12-volt DC operation Environmental sealed front face Text alarm/event descriptions Digital indication for: RPM DC Volts Operating Hours Oil Pressure (psi) Coolant Temperature Volts (L-L & L-N). frequency (Hz) Amps (per phase & average) Power Factor (per phase & average) kW (per phase,average & percent) kVA (per phase,average & percent) kVAr (per phase,average & percent) kW-hr (total) kVAr-hr (total) Warning/shutdown with common LED indication of shutdowns for: Low Oil pressure Low Coolant temp alarm (detects jacket water heater failure) High Coolant temperature shutdown EFTA00798773 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION I SCOPE OF SUPPLY (continued) Standard Consist for C7.1 PGABR (continued) CONTROL PANELS (continued) Programmable protective relaying functions: Generator phase sequence Over/Under voltage (27/59) Over/Under Frequency (81 o/u) Reverse Power (KW) (32) Reverse Reactive Power (kVAr) (32RV) Overcurrent (50/51) Communications Customer DATA link (Modbus RTU) RS485 Serial DATA link (terminals only) 8 programmable digital outputs available 2 relays pre-programmed 8 programmable digital inputs available 2 pre-programmed CIRCUIT BREAKERS UL/CSA listed mainline breaker Single Breaker 100% Rated 3-pole with solid neutral NEMA 1 steel enclosure Electrical stub-up area directly below circuit breaker COOLING SYSTEM Radiator and cooling fan complete with protective guards Standard ambient temperatures up to 50degC (122degF) 50% coolant antifreeze/corrosion inhibitor Coolant reservoir EFTA00798774 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION I SCOPE OF SUPPLY (continued) Standard Consist for C7.1 PGABR (continued) GENERATORS GENERATOR SET Complete system designed and built at ISO 9001:2000 certified facilities Factory tested to design specifications at full load conditions and all protective devices and control functions simulated and checked GENERATOR Insulation system, class H Drip proof generator air intake (NEMA 2,IP23) Electrical design in accordance with BS5000 Part 99,EN61000-6, IEC60034-1,NEMA MG-1.33 EQUIPMENT FINISH All electroplated hardware Anticorrosive paint protection High gloss polyurethane paint for durability and scuff resistance QUALITY STANDARDS BS4999,BS5000,855514,EN61000-6.IEC60034,NEMA MG-1.33, NFPA 110 (with optional equipment) LITERATURE / DOCUMENTATION Operation and maintenance manual pack and OMM Storage Compartment Wiring diagrams included MOUNTING SYSTEM Heavy-duty fabricated steel base with lifting points Anti-vibration pads to ensure vibration isolation Complete OSHA guarding Stub-up pipe ready for connection to silencer pipe work Flexible fuel lines to base with NPT connections GENERAL Factory Test Report EFTA00798775 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION I SCOPE OF SUPPLY (continued) Item 1 One (1) Caterpillar Model D125 — 8 diesel engine generator set with the following: Selected Caterpillar Options 208 / 120 v. 3 Phase 60 Hz, 114 kW UL 2200 Listed Package Gen Set EPA Stationary Emergency Prime Power ENGINE Air Inlet System Single element Air Filter — Light Duty Cooling System Standard Radiator Coolant Heater TECHNICAL: On at 100 and off at 120 degree F Low Coolant Level Shutdown GENERATOR Generator Frame: LC3114J Attunement 4545283 Excitation Permanent Magnet Excitation Main Breaker 400 Amp First Breaker 100% Rated UL ENCLOSURE Enclosure Sound Attenuated Enclosure 12 (White) TECHNICAL: Foam enclosure with endbox Critical Silencer Audible Alarm Panel Mounted Audible Alarm Emergency Stop External Emergency Stop Button STARTING SYSTEM Battery Wet Battery Battery Charger NFPA Batter Charger UL 10A 120 VAC EFTA00798776 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION I SCOPE OF SUPPLY (continued) Item 1 One (1) Caterpillar Model D125 — 8 diesel engine generator set with the following: Selected Caterpillar Options (continued) GROUND RELAY SYSTEM Ground Fault Relay TECHNICAL: GROUND FAULT INDICATION CONTROL PANEL OPTIONS Generator Control EMCP 4.2 Generator Control Panel Control Panel Options Box Accessory Connections NFPA 110 Bundle Bundled option to include: Low Coolant level shut down Low Coolant temperature alarm Panel mounted audible alarm NFPA Battery Charger EFTA00798777 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION I SCOPE OF SUPPLY (continued) Documentation Submittals Electronic Copy One (1) Operation and Maintenance Manuals One (1) Parts Disc One (1) Start Up and Commissioning By Others Caterpillar Warranty Standard Caterpillar Prime Power Warranty EFTA00798778 Warren CAT WARREN Mi 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION II GENERATOR PACKAGE EFTA00798779 C7.1 Generator Set Electric Power CAT® Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness. Image shown may not reflect actual configuration Specifications Generator Set Specifications Rating 114 ekW (142.5 kVA) Voltage 480 Volts Frequency 60 Hz Speed 1800 rpm Generator Set Configurations U.S. EPA Certified for Stationary Emergency Use Only Emissions/Fuel Strategy (Tier 3 Nonroad Equivalent Emission Standards) Engine Specificatio Engine Model C7.1 In-line 6, 4-cycle diesel Bore 105 mm 4.13 in Displacement 7.01 L 427.8 in3 Stroke 135 mm 5.31 in Compression Ratio 16.7:1 Aspiration Turbocharged Air-to-Air-Aftercooled Governor Type Electronic Fuel System Common Rail Package Dimensions* Length 3039mm 119.7 in Width 1110 mm 43.7 in Height 1476 mm 58.1 in Weighty 1500 kg 3307 lb *Note: For reference only — do not use for installation design. Please contact your local dealer for exact weight and dimensions. tWeight includes: Oversize generator, skid base, circuit breaker, oil, and coolant. LEHE0889-02 Page 1 of 7 EFTA00798780 C7.1 Generator Set Electric Power CAT® Benefits & Features Car Diesel Engine • Reliable, rugged, durable design • Four-stroke cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight • Electronic engine control Generator • Matched to the performance and output characteristics of Cat engines • Industry-leading mechanical and electrical design • Industry-leading motor starting capabilities • High efficiency Cat EMCP Control Panel The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP 4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP 4 systems can be further customized to meet your needs through programming and expansion modules. Seismic Certification • Seismic certification available • Anchoring details are site specific, and are dependent on many factors such as generator set size, weight, and concrete strength IBC certification requires that the anchoring system used is reviewed and approved by a professional engineer Seismic certification per applicable building codes: IBC 2006, IBC 2009, IBC 2012, IBC 2015 Design Criteria • The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response • Cooling system designed to operate in 50`C/122T ambient temperatures with an air flow restriction of 0.5 in. water UL 2200/CSA — Optional • UL 2200 Listed • CSA Certified Certain restrictions may apply. Consult with your Cat dealer. Single-Source Supplier Fully prototype tested with certified torsional vibration analysis. Worldwide Product Support Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•Ss" program cost-effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products. LEHE0889-02 Page 2 of 7 EFTA00798781 C7.1 Generator Set Electric Power CAT® Standard Equipment Air Inlet • Dry replaceable paper element type with restriction indicator Cooling • Radiator and cooling fan complete with protective guards • Standard ambient temperatures up to 50°C (122°F) Exhaust • Exhaust flange outlet Fuel • Primary and secondary fuel filters • Fuel priming pump • Flexible fuel lines Generator • Matched to the performance and output characteristics of Cat engines • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time • IP23 protection • Integrated Voltage Regulation Governor • Electronic governor — ADEM TPA A4 Control Panels • EMCP 4.2 Series generator set controller Mounting • Rubber vibration isolators Starting/Charging • 12 volt starting motor • Batteries with rack and cables General • Paint — Caterpillar Yellow except rails and radiators gloss black LEHE0885-02 Page 3 of 7 EFTA00798782 C7.1 Generator Set Electric Power CAT® Optional Equipment Exhaust • Industrial, residential, critical mufflers Generator • Excitation: [ ] Permanent Magnet Excited (PM) ] Internally Excited (lE) • Anti-condensation heater Oversize and premium generators Starting/Charging Battery charger — UL 10 amp • Battery disconnect switch Jacket water heater General • UL 2200 • CSA Certification Enclosures: sound attenuated, weather protective • Sub-base dual wall UL Listed fuel tanks • Automatic transfer switches (ATS) LEHE0889-02 Page 4 of 7 EFTA00798783 ELECTRIC POWER — Technical Spec Sheet STANDARD C7.1 CAT® 114 ekW/ 142.5 WA/ 60 Hz/ 1800 rpm/ 480V/ 0.8 Power Factor Rating Type: PRIME Emissions: U.S. EPA Certified for Stationary Emergency Use Only (Tier 3 Nonroad Equivalent Emission Standards) D125-8 114 ekW/ 142.5 kVA 60 Hz/ 1800 rpm/ 480V Image shown may not reflect actual configuration Package Performance Generator Set Power Rating with Fan @ 0.8 Power Factor 114 ekW Generator Set Power Rating 142.5 kVA Fuel Consumption 100% Load With Fan 35.2 Uhr 9.3 g/hr 75% Load With Fan 28.2 Uhr 7.4 g/hr 50% Load With Fan 20.3 Uhr 5.4 g/hr Cooling System' Engine Coolant Capacity 9.5 L 2.5 gal Radiator Coolant Capacity 11.5 L 3.0 gal Engine Coolant Capacity with Radiator/Exp Tank 21.0 L 5.5 gal Air Flow Restriction (System) 0.12 kPa 0.48 in Water Combustion Air Inlet Flow Rate 13.9 ms/min 490.9 cfm Exhaust System Exhaust Stack Gas Temperature 439°C 822°F Exhaust Gas Flow Rate 28.8 ms/min 1017 cfm Exhaust System Backpressure (maximum allowable) 15.0 kPa 60.2 in water Exhaust Flange Size (internal diameter) 89.0 mm 3.5 in LEHE0889-02 Page 5 of 7 EFTA00798784 ELECTRIC POWER — Technical Spec Sheet STANDARD C7.1 CAT® 114 ekW! 142.5 kVA/ 60 Hz! 1800 rpm! 480W 0.8 Power Factor Rating Type: PRIME Emissions: U.S. EPA Certified for Stationary Emergency Use Only (Tier 3 Nonroad Equivalent Emission Standards) Heat Rejection Heat Rejection to Coolant (total) 69.0 kW 3924 Btu/min Heat Rejection to Exhaust (total) 120.0 kW 6796 Btu/min Heat Rejection to Aftercooler 30.0 kW 1689 Btu/min Heat Rejection to Atmosphere from Engine 26.0 kW 1496 Btu/min Heat Rejection to Atmosphere from Generator 8.8 kW 500.4 Btu/min Alternator Motor Starting Capability @ 30% Voltage Dip 363 skVA Frame LC3114G Temperature Rise 105°C 189°F Excitation Self Excited Sump Refill with Filter 17.5 L 4.6 gal Emissions (Nominal)' NOx + HC 4.0 g/kW-hr CO 1.0 g/kW-hr PM 0.2 g/kW-hr 'For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to the existing restriction from the factory. 2Generator temperature rise is based on a 40°C (104°F) ambient per NEMA MG1-32. 'The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% Prime load. This information should not be used for permitting purposes and is subject to change without notice. Contact your Cat dealer for further details. LEHE0889-02 Page 6 of 7 EFTA00798785 ELECTRIC POWER — Technical Spec Sheet STANDARD C7.1 CAT® 114 ekW! 142.5 kVA/ 60 Hz/ 1800 rpm! 480W 0.8 Power Factor Rating Type: PRIME Emissions: U.S. EPA Certified for Stationary Emergency Use Only (Tier 3 Nonroad Equivalent Emission Standards) DEFINITIONS AND CONDITIONS Applicable Codes and Standards: AS1359, CSA C22.2 No 100-04, UL142, UL489, UL601, UL869, UL2200, NFPA 37, NFPA 70, NFPA 99, NFPA 110, IBC,IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, NEMA MG 1-33, 72/23/EEC, 98/37/EC, 2004/108/EC. PRIME: Output available with varying load for an unlimited time. Average power output is 70% of the prime power rating.Typical peak demand is 100% of prime rated ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year. Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions. Fuel Rates are based on fuel oil to specification EPA 2D 89.330-96 with a density of 0.845 - 0.850 kg/L (7.052 - 7.094 lbs/U.S. gal.) @ 15°C (59°F) and fuel inlet temperature 40°C (104°F). Additional ratings may be available for specific customer requirements, contact your Cat representative for details. www rat-FlartriePnwor relit Performance No.: P4392C-00 O2016 Caterpillar Feature Code: NAC160P All rights reserved. Generator Arrangement: 4545273 Materials and specifications are subject to change without notice. Date: 09/13/2016 The International System of Units (SI) is used in this publication. Source Country: U.S. CAT. CATERPILLAR. their respective logos. ADEM. S.O.S, 'Caterpillar Yellow'. the "Power Edge" trade dress as well as corporate and product identity used LEHE0BB9-01 herein, are trademarks of Caterpillar and may not be used without permission. EFTA00798786 Warren CAT WARREN CAT 15 North Meridian Avenue Oklahoma City, Oklahoma 73127 SECTION III ALTERNATOR DATA EFTA00798787 7/18/2018 Caterpillar Generator Data GENERATOR DATA JULY 18, 2018 For Help Desk Phone Number, Selected Model Engine: C7.I Generator I. aloe: LC31143 Genset Rating (kW): 114.0 Line Voltage: 208 Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120 Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5 Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current Version: 41764 /41736 /42059 1633 Spec information Generator Specification Generator Efficiency Frame: LC3114J Type: LC No. of Bearings: I Per Unit Load kW Efficiency % Winding Type: RANDOM WOUND Flywheel: 11.5 0.25 28.5 91.1 Connection: PARALLEL STAR Housing: 3 0.5 57.0 93.5 Phases: 3 No. of Leads: 12 0.75 85.5 94.0 Poles: 4 Wires per Lead: I 1.0 114.0 93.8 Sync Speed: 1800 Generator Pitch: 0.6667 1.1 125.4 93.6 Reactances Per Unit Ohms SUBTRANSIENT - DIRECT AXIS ri d 0.0929 0.0282 SUBTRANSIENT - QUADRATURE AXIS ri g 0.1835 0.0557 TRANSIENT - SATURATED rd 0.1545 0.0469 SYNCHRONOUS - DIRECT AXIS Xd 3.2147 0.9760 SYNCHRONOUS - QUADRATURE AXIS X4 1.9288 0.5856 NEGATIVE SEQUENCE X2 0.1380 0.0419 ZERO SEQUENCE X0 0.0033 0.0010 lime Constants Seconds OPEN CIRCUIT TRANSIENT - DIRECT AXIS Tdo 2.0791 SHORT CIRCUIT TRANSIENT - DIRECT AXIS Td 0.1000 OPEN CIRCUIT SUBSTRANSIENT - DIRECT AXIS T"do 0.0167 SHORT CIRCUIT SUBSTRANSIENT - DIRECT AXIS T"d 0.0100 OPEN CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T"q0 0.1052 SHORT CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T"q 0.0100 EXCITER TIME CONSTANT; 0.0300 ARMATURE SHORT CIRCUIT Ta 0.0150 Short Circuit Ratio: 0.37 Stator Resistance = 0.0118 Ohms Field Resistance = 3.29 Ohms Voltage Regulation Generator Excitation Voltage level adjustment: +/- 5.0% No Load Full Load, (rated) pf Voltage regulation, steady state: +/- 0.5% Series Parallel Voltage regulation with 3% speed change: +1- 1.0% Excitation voltage: 5.82 Volts 28.27 Volts Volts Waveform deviation line - line, no load: less than 2.0% Excitation current 0.45 Amps 1.8 Amps Amps Telephone influence factor: less than 50 https://tmiwebelassie.cat.corn/tmi/servlet/TMIDirector?Action=openvAndow&log=genXml0ata&type=RNGenDataRelNum&relno=8.selection=&unitType... 1/8 EFTA00798788 7/18/2018 Caterpillar Generator Data Selected Model Engine: C7.I Generator Frame: LC3114J Genset Rating (kW): 114.0 Line Voltage: 208 Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120 Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5 Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current Version: 41764 /41736 142059 1633 Generator Mechanical Information Center of Gravity Dimension X 0.0 nun 0.0 IN. Dimension Y 0.0 nun 0.0 IN. Dimension Z 0.0 nun 0.0 IN. • "r is measured from driven end of generator and parallel to rotor. Towards engine fan is positive. See General Information for details • "Y" is measured vertically from rotor center line. Up is positive. • 7" is measured to left and right of rotor center line. To the right is positive. Generator WT = 0 kg ■ Rotor WT = 0 kg * Stator WT = 0 kg 0.0 LB 0.0 LB 0.0 LB Rotor Balance = 0.0508 mm deflection PTP Overspeed Capacity = 125% of synchronous speed HIOVV\V IVIKM Generator Torsional Data 0 c> J1 = Coupling J2 = Rotor J3 = Exciter and Fan TOTAL J = J1 +J2 + J3 End ICI = Shaft Stiffness between 1C2 = Shaft Stiffness between JI + J2 (Diameter 1) J2 +J3 (Diameter 2) JI ict Min Shaft Dia I J2 K2 Min Shaft Dia 2 J3 0.0 LB IN. 52 0.0 MLB IN./rad 0.0 IN. 0.0 LB IN. s2 0.0 MLB IN./rad 0.0 IN. 0.0 LB IN. s2 0.0 N m 52 0.0 MN mired 0.0mm 0.0 N m 52 0.0 MN m/rad 0.0mm 0.0 N m s2 Total .1 0.0 LB IN. s2 0.0 N m52 Selected Model Engine: C7.1 Generator Frame: LC31143 Genset Rating (kW): 114.0 Line Voltage: 208 Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120 Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5 Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current Version. 4170/41736 /43059 /633 hupsfitmiweleclassiocat.com/tmi/servleUTMIDirector?Action=openvAndownlog=genXmiDatantype=ftNGenDataftelNum&relno=8.selection=&unitType... 2/8 EFTA00798789 7/18/2018 Caterpillar Generator Data Generator Cooling Requirements - Temperature - insulation Data Cooling Requirements: Temperature Data: (Ambient 40 0C) I lest Dissipated: 7.5 kW Stator Rise: 105.0°C Air Flow: 18.0 m3/min Rotor Rise: 105.0°C Insulation Class: Ii Insulation Reg. as shipped: 100.0 MI/ minimum at 40 °C Thermal Limits of Generator Frequency: 60 Hz Line to Line Voltage: 208 Volts B BR 80/40 141.5 kVA F BR -105/40 161.0 kVA H BR - 125/40 177.0 kVA F PR - 130/40 177.0 kVA H PR -150/40 187.5 kVA H PR27 - 163/27 194.5 kVA Selected Model Engine: C7.I Generator Frame: LC31143 Genset Rating (kW): 114.0 Line Voltage: 208 Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120 Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5 Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current %miens:41764 /41736 /42059 /633 Starting Capability & Current Decrement Motor Starting Capability (0.6 pf) Percent Motor Starting SKVA Volt Dip 21 23 40 44 5.0 68 73 O . 35 93 10.0 30 119 123 147 15.0 25 177 173 , 20 209 20.0 C 242 22.5 ;I' 15 278 25.0 I. 317 273 10 358 30.0 5 402 323 450 35.0 0 501 373 0 leo zoo 300 460 560 557 40.0 SKVA https://tmiwebelassie.eat.corn/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlOata&type=RNGenDataRelNum&relno=aselection=&unitrype... 3/8 EFTA00798790 7/18/2018 Caterpillar Generator Data Current Decrement Data E Time AMP Current Decrement Cycle 0.0 4232 1.0 2,505 4,000 2.0 1.918 3,500 3.0 1.587 4.0 1.336 3,000 5.0 1.126 2,500 7.5 n9 10.0 463 2,000 12.5 286 1,500 15.0 185 20.0 98 1,000 25.0 69 500 30.0 57 35.0 53 0 40.0 51 0 10 20 30 40 45.0 50 E Time Cycle Instantaneous 3 Phase Fault Current: 4232 Amps Instantaneous Line - Line Fault Current: 2945 Amps Instantaneous Line - Neutral Fault Current: 5033 Amps Selected Model Engine: C7. I Generator Frame: LC31I4J Genset Rating (kW): 114.0 Line Voltage: 208 Fuel: Diesel Generator Arrangement: 4545283 Genset Rating (kVA): 142.5 Phase Voltage: 120 Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 395.5 Duty: PRIME Connection: PARALLEL STAR Application: EPG Status: Current Version: 41764 /41736 /42059 /633 Generator Output Characteristic Curves Open Circuit Curve Open Circuit 300 Field Line • Current Line Volt 250 44 0.0 0 2.7 125 3.2 146 3.8 166 150 4.4 187 5.2 208 tal 100 6.3 229 8.2 250 z 11.4 270 50 17.6 291 0 0 5 10 15 Field Current httpsditmiwebelassie.cat.com/tmi/sarvlet/TMIDIrector?ActIon=opanvAndow&log=genXmlOata&type=RNGenDalaReINum&reino=8.salection=&unItType... 4/8 EFTA00798791 7/18/2018 Caterpillar Generator Data Short Circuit Curve Short Circuit Field Armature 500 Currant Current 0.0 0 400 8.7 237 7
ℹ️ Document Details
SHA-256
7ac5d8654812870ce22909f449953a6f78aac79d9ca04191867005527a1ca3ff
Bates Number
EFTA00798769
Dataset
DataSet-9
Document Type
document
Pages
105

Comments 0

Loading comments…
Link copied!