From: brice gordon <
Sent: Monday, Augus , .
To: [email protected]
Cc: Richard Kahn
Subject: Fwd: Generator #2
Basically
We need to refurbish on= generator backend , ($8000.00) if you wish to have at least one backup ge=erator online for
hurricane season New Backends for both Ge=sets due Mid October How do you wish to proceed ?
Sent from my iPhone
Begin forwarded message:<=r>
From: michael glidden
Date:<=b> August 6, 20
To: brice gordon
Good da=.
As discussed on site, the problem with the emergency gene=ator #2 is with the exciter coil and the companion
diode plate.
<=pan> When we had the failure of #2 during the rehab of #1 the rear end was t=ken off #1 and quickly
refurbished to get it installed on the failed unit s= as to have back up power.
Due to the emergency time line a=complete disassembly of the #1rear end did not happen. This would have
add=d a week or more to the timeline of getting back on line. Unfortunately tha= gamble did not pay off as we now are
forced to do exactly the work that wa= skipped over in the name of expediency due to the fact of a failure within=the
diode plate itself which requires a complete disassembly of the rear en= to repair.
This will need to take place off of LSJ at a r=pair facility.
Work can begin immediately on the original f=iled rear end as it is currently at the repair facility. A quote of
15,000.=0 has been provided and will include a warranty on the repairs to be made.<=span>
Omega is the company providing the quote and has said a depo=it of $8,000.00 is required prior to starting.
I will forwa=d the formal quote and company information shortly.
Until t=is work can be completed and the refurbished unit installed there will be n= generator back up for power
on LSJ.
Regar=s,
MG.