📄 Extracted Text (484 words)
METROPOLITAN TESTING AND BALANCING CORP.
22-14 124TH STREET
COLLEGE POINT, N.Y. 11356
OFFICE (718) 747-5545 FAX (718) 747-5547
DATE: 5/21/13
VENTILATION TEST REPORT
EPSTEIN RESIDENCE
9 EAST 71ST STREET
NEW YORK, N.Y.
3RD FLOOR
PREPARED FOR
A.D. WINSTON SERVICECORP.
43-15 36"1 STREET
L.I.C., N.Y. 11101
JOB NO. 4582
EFTA01107704
METROPOLITAN TESTING AND
BALANCING CORP.
Date 5/21/13
Page 1 of 3
Project 9 EAST 71ST STREET
System No MASTER BEDROOM UNIT (MB UNIT1 Flood! ON el FLOOR (SERVES 3RD)
AIR DISTRIBUTION TEST SHEET
FAN MAKE MAGIC AIRF. RATED ACTUAL
SIZE 120-BVW / BVX-A LINE VOLTS 208/3/60 208
7.4/7.4/7.4 (WITH AC-3 ON )
MOTOR HP 3 MOTOR AMPS 9.9 8.1/8.1(7.9 (WITH AC-3 OFF)
RPM 1775
REQUIRED ACTUAL
LW (Willi AL-3 UN)
STATIC PRESSURE:
FAN RPM N.A. 1283 (WMI AC-3 OFF)
2192 (WITH AC-3 ON)
SUCTION SEE SP IN. w.O.
SYSTEM CFM 2100 2783 (WITH AC-3 OFF)
DISCHARGE PROFILE. IN WG
Terminal Terminal Design Final
Number Type Size Factor FPM CFM FPM CFM Static Pressure (in.w.g.)
AC-3 ON
PPLY
Fr-MB SU
MAIN DUCT 26X15 2.7 777 2100 812 2192 +2.0
AC-3 OFF
PT-MB MAIN
SUPPLY DUCT 26X15 2.7 777 2100 1031 2783 +3.0
AC-I OFF*
ACCESS
DOOR
IDOWNSTPJAI
REMOVED
PT-MB SUPPLY
MAIN DUCT 26X15 2.7 777 2100 1337 3610 +1.3
Remarks:
EFTA01107705
METROPOLITAN TESTING AND
BALANCING CORP.
Date 5/21/11
Page 2 of 3
Project 9 EAST 71ST STREET
System No MASTER BEDROOM UNIT (MB UNIT) Floor!! 3RD
AIR DISTRIBUTION TEST SHEET
Terminal Room Terminal _ Design Final
Number Number Type Size Factor FPM CFM FPM CFM Remarks
WITH
AC-3 ON
1 SG 42X2 NA 291
2 SG 42X2 NA 263
3 SG 38X2 NA 299
4 FG 5'0" NA 740
5 FG 5'0" NA 745
TOTAL 2100 2338
WITH
AC-3 OFF
1 SG 42X2 NA 349
2 SG 42X2 NA 322
3 SG 38X2 NA 349
4 FG 5'0" NA 900
5 FG Sr NA 890
TOTAL 2100 2810
Remarks:
EFTA01107706
METROPOLITAN TESTING AND
BALANCING CORP.
Date 5/21/13
Page of 1
'roject Name 9 EAST 71ST STREET
STATIC PRESSURE PROFILE
o.a. dampers
I
mix. box
•~7•
g
UNIT a b c d e f g h j
•M5 UNIT -.88 X X X -1.0 X X X +2.0
••MB UNIT -.30 X X X -.46 X X X +3.0
:marks *READINGS WITH AC-3 ON **READINGS WITH AC-3 OFF
EFTA01107707
16x8 TOILET EXH.
UP TO EF-8
550 CFM 24x5 DN.
16x6 UP
12x4 TAP
140 CFM EA
TYP. FOR 2
12-Wx6-Hx3.-
A.L. PLENUM
-12x6
TYPICAL FOR 3,- I
16. 1Vx6-Hx4.-41.
A.L. PLENUM
24x10 SUPPLY GRILLES
1
170 CFM
10x6 6 \ 18'Wx10-1-ix5.-0"L
A.L.PLENUM
16x10 R.A. OPNG. TYPICAL FOR 2
ABOVE CLG. 500
12%8' TAP
W/ C.O.D. - 325
TYPICAL FOR 2
10x6 UP
250 CFM UP TO
GUEST SITTING RM
-16x10 R.A. OPNG.
ABOVE CLG. 500 CFM
28x10
18-Wx8"Hx4.-0'L
A.L. PLENUM©
14-x6-
TAp
W/ CO D. - 290 CFM
28x10 R.A. OPGN.
ABOVE CLG. 670 CFM
x6
EFTA01107708